Title of article :
Theoretical and experimental evaluation of an indirect-fired GAX cycle cooling system
Author/Authors :
V.H. G?mez، نويسنده , , A. Vidal، نويسنده , , R. Best، نويسنده , , O. Garcia-Valladares، نويسنده , , N. Vel?zquez، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Abstract :
A theoretical and experimental evaluation of an indirect-fired GAX-Prototype Cooling System (GAX-PCS), using ammonia–water as the working fluid, is presented. The GAX-PCS was designed for a cooling capacity of 10.6 kW (3 tons). A simulation model was developed, calibrated and validated with experimental values in order to predict the performance of the system outside the design parameters. Experimental results were obtained using thermal oil, at temperatures from 180 to 195 °C, as heating source. An internal heat recovery in the system of ∼55% with respect to the total heat supplied in the generator was obtained. Also the performance of the GAX absorption system, integrated to a micro gas turbine (MGT) as a cogeneration system was simulated. Overall efficiencies for the cogeneration system from 29% to 49% were obtained for cooling loads from 5 kW to 20 kW, respectively. With the theoretical and experimental study of the proposed cycle, it is concluded that the GAX-PCS presents potential to compete technically in the Mexican air conditioning market.
Keywords :
Ammonia–water , Waste heat , Air conditioning , Microturbine , absorption
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering