Title of article :
Improving two-phase refrigerant distribution in the manifold of the refrigeration system
Author/Authors :
Mao-Yu Wen، نويسنده , , Chin-Ho Lee، نويسنده , , Jui-Chen Tasi، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
10
From page :
2126
To page :
2135
Abstract :
This study presents an experimental investigation to improve the two-phase refrigerant distribution in the manifold of the refrigeration (R-134a) system. The tests were conducted at the nominal inlet pressure of 173.5 kPa and mass flux of 130–145 kg/m2 s. Three different distributor configurations (Venturi tube connected with a smooth tube, Venturi tube connected with an internally–spirally micro-finned tube, and distributor within a roller) were selected. In the experiment, the effects of the outer-wall temperatures and pressures of the exits in the manifold, the cooling capacity (C) and coefficient of performance (COP) on two-phase flow distribution for the present study were displayed and discussed. In order to understand that flow distribution of two-phase refrigerant in the manifold, the flow visualization at the exit manifold of the distributor was made. It was found that the Venturi tube connected with the internally–spirally micro-finned tube got the best distribution efficiency, and resulted in the best coefficient of performance.
Keywords :
Two-phase refrigerant distribution , Three different distributors , Refrigeration system
Journal title :
Applied Thermal Engineering
Serial Year :
2008