Title of article :
Experimental performance of R432A to replace R22 in residential air-conditioners and heat pumps
Author/Authors :
Ki-Jung Park، نويسنده , , Yun-Bo Shim، نويسنده , , Dongsoo Jung، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Pages :
4
From page :
597
To page :
600
Abstract :
In this study, thermodynamic performance of R432A and HCFC22 is measured in a heat pump bench tester under both air-conditioning and heat pumping conditions. R432A has no ozone depletion potential and very low greenhouse warming potential of less than 5. R432A also offers a similar vapor pressure to HCFC22 for ‘drop-in’ replacement. Test results showed that the coefficient of performance and capacity of R432A are 8.5–8.7% and 1.9–6.4% higher than those of HCFC22 for both conditions. The compressor discharge temperature of R432A is 14.1–17.3 °C lower than that of HCFC22 while the amount of charge for R432A is 50% lower than that of HCFC22 due to its low density. Overall, R432A is a good long term ‘drop-in’ environmentally friendly alternative to replace HCFC22 in residential air-conditioners and heat pumps due to its excellent thermodynamic and environmental properties.
Keywords :
Natural refrigerants , Dimethylether , Propylene , Air conditioners , R432A , Heat pumps
Journal title :
Applied Thermal Engineering
Serial Year :
2009
Journal title :
Applied Thermal Engineering
Record number :
1041838
Link To Document :
بازگشت