• Title of article

    Environmental performance and economic analysis of all-variable speed chiller systems with load-based speed control

  • Author/Authors

    F.W. Yu، نويسنده , , K.T. Chan، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    9
  • From page
    1721
  • To page
    1729
  • Abstract
    There are increasing views on implementing all-variable speed chiller plants in place of conventional constant speed plants. Supporters of these views claim that all-variable speed chiller systems can operate much more efficiently at part load in response to changes in building cooling load. This paper introduces load-based speed control for all-variable speed plants to optimize their environmental performance. Thermodynamic-behaviour chiller system models were developed to perform environmental assessment (in terms of annual electricity and water consumption) for typical constant speed and all-variable speed chiller systems operating for the cooling load profile of a local office building. Operating cost differences between the two systems were calculated and compared in an economic analysis. Applying load-based speed control to the variable speed chiller plant can decrease the annual total electricity use by 19.7% and annual water use by 15.9% relative to the corresponding constant speed plant. The significance of this study is to provide more insights into how to make chiller systems more sustainable.
  • Keywords
    Water-cooled chiller , Variable speed , simulation , Electricity and water consumption
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2009
  • Journal title
    Applied Thermal Engineering
  • Record number

    1041973