Title of article :
Flow boiling heat transfer coefficient of R-134a/R-290/R-600a mixture in smooth horizontal tubes using varied heat flux method
Author/Authors :
B. Raja، نويسنده , , D. Mohan Lal، نويسنده , , R. Saravanan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
An experimental study on in-tube flow boiling heat transfer of R-134a/R-290/R-600a refrigerant mixture has been carried out under varied heat flux test conditions. The heat transfer coefficients are experimentally measured at temperatures between −8 and 5 °C for mass flow rates of 3–5 g s−1. Acetone is used as a hot fluid which flows in the outer tube of diameter 28.57 mm while the refrigerant mixture flows in the inner tube of diameters 9.52 and 12.7 mm. By regulating the acetone flow conditions, the heat flux is maintained between 2 and 8 kW/m2 and the pressure of the refrigerant is maintained between 3.2 and 5 bar. The comparison of experimental results with the familiar correlations shows that the correlations over predict the heat transfer coefficients for this mixture when stratified and stratified-wavy flow prevail. Multiple regression technique is used to evolve and modify existing correlations to predict the heat transfer coefficient of the refrigerant mixture. It is found that the modified version of Lavin–Young correlation (1965) predicts the heat transfer coefficient of the considered mixture within an average deviation of ±20.5 %.
Keywords :
correlation , Refrigerant mixture , Flow boiling , Heat transfer coefficient , Stratified flow , Stratified-wavy , Multiple regression , HC blend
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering