Title of article :
Thermoelectric air-cooling module for electronic devices
Author/Authors :
Yu-Wei Chang a، نويسنده , , Chih-Chung Chang، نويسنده , , Ming-Tsun Ke، نويسنده , , Sih-Li Chen، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
This article investigates the thermoelectric air-cooling module for electronic devices. The effects of heat load of heater and input current to thermoelectric cooler are experimentally determined. A theoretical model of thermal analogy network is developed to predict the thermal performance of the thermoelectric air-cooling module. The result shows that the prediction by the model agrees with the experimental data. At a specific heat load, the thermoelectric air-cooling module reaches the best cooling performance at an optimum input current. In this study, the optimum input currents are from 6 A to 7 A at the heat loads from 20 W to 100 W. The result also demonstrates that the thermoelectric air-cooling module performs better performance at a lower heat load. The lowest total temperature difference-heat load ratio is experimentally estimated as −0.54 W K−1 at the low heat load of 20 W, while it is 0.664 W K−1 at the high heat load of 100 W. In some conditions, the thermoelectric air-cooling module performs worse than the air-cooling heat sink only. This article shows the effective operating range in which the cooling performance of the thermoelectric air-cooling module excels that of the air-cooling heat sink only.
Keywords :
Heat sink , Thermoelectric air-cooling module , Thermoelectric cooler
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering