Title of article :
Study on performance of a heat pump water heater using suction stream liquid injection
Author/Authors :
Cao Feng، نويسنده , , Fei Jiyou، نويسنده , , Xing Ziwen، نويسنده , , Li Liansheng، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Abstract :
Liquid refrigerant injection into a suction line is an effective and practical method to reduce the discharge temperature when a scroll compressor operates at high compression ratios. In the present study, correlations among the compressor suction temperature, discharge temperature, heat pump heating capacity, power consumption, coefficient of performance (COP) and the quantity of suction liquid injection are established. The paper presents experimental analysis and a comparison with calculated results of the heat pump water heater (HPWH) performance with suction liquid injection in different conditions. It is found that the suction liquid injection explicitly lowers the discharge temperature of the compressor and the heating capacity of the unit, but the power consumption increases with COP decreasing. In addition, the highest injection ratio must be controlled fewer than 5%. The suction liquid injection has a better effect on the HPWH at the temperature ranging from −15 °C to 20 °C. Within this temperature range, the 5% ratio suction liquid injection decreases the discharge temperature of the compressor by 10 °C, while the heating capacity of the HPWH decreases by less than 5%, power consumption increases by less than 1.5%, and COP decreases by less than 7%.
Keywords :
performance , Liquid , Injection , Scroll compressor , Heat pump
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering