• Title of article

    An experimental study of axial conduction through a thermosyphon pipe wall

  • Author/Authors

    Wei Guo، نويسنده , , Darin W. Nutter، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2009
  • Pages
    6
  • From page
    3536
  • To page
    3541
  • Abstract
    The effect of the axial conduction through the pipe wall on the performance of a thermosyphon was experimentally investigated in this study. Two 2-phase closed thermosyphons were tested; each had the same dimensions, materials and partially filled with R134a. The only difference between them was that one had a thermal break within the adiabatic section that resisted axial conduction between the evaporator and the condenser sections. The thermosyphons were heated by a constant-temperature hot bath and cooled by water via a concentric heat exchanger. The experiments were performed for different bath temperatures and different fill ratios. It was found that the axial conduction through the pipe wall caused an increase in the overall heat transfer coefficient, evaporation heat transfer coefficient and condensation heat transfer coefficient of the thermosyphon. However, the fraction of heat transfer associated with axial conduction decreased as the heat flux increased. For small heat flux (Tb = 30 °C), the increment of the evaporation and condensation heat transfer coefficient contributed by axial conduction reached 100% and 25%, respectively. For high heat flux (Tb = 60 °C), the increment was negligible (less than 1%).
  • Keywords
    Fill ratio , R134a , Heat transfer coefficient , Thermal break , Thermosyphon
  • Journal title
    Applied Thermal Engineering
  • Serial Year
    2009
  • Journal title
    Applied Thermal Engineering
  • Record number

    1042359