Title of article :
Performance assessment of a direct expansion air conditioner working with R407C as an R22 alternative
Author/Authors :
M. Fatouh، نويسنده , , Talaat A. Ibrahim، نويسنده , , A. Mostafa، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Abstract :
This paper presents an experimental investigation of a direct expansion air conditioner working with R407C as an R22 alternative. Experiments are conducted on a vapor compression refrigeration system using air as a secondary fluid through both the evaporator and the condenser. The influences of the evaporator air inlet temperature (20–32 °C), the evaporator air flow rate (250–700 m3/h) and the evaporator air humidity ratio (9 and 14.5 gwv/kga) at the condenser air temperature and volume flow rate of 35 °C and 850 m3/h, respectively on the system performance are investigated. Experimental results revealed that the evaporator air inlet temperature has pronounced effects on the air exit temperatures, pressures of the evaporator and the condenser, cooling capacity, condenser heat load, compressor pressure ratio and the COP of both refrigerants at humidity ratios of 9 and 14.5 gwv/kga. Significant effects of the evaporator air flow rate are also gathered on the preceding parameters at the same values of mentioned-humidity ratios. The best performance, in terms of operating parameters as well as COP, can be accomplished using R22 compared to R407C. The inlet humidity ratio affects dramatically the performance of vapor compression system using R22 and R407C. The raising up humidity ratio from 9 to 14.5 gwv/kga leads to an augmentation in the average cooling capacity by 29.4% and 38.5% and an enhancement in the average COP by 30% and 24.1% for R22 and R407C, respectively.
Keywords :
R22 , R407C , COP , Air conditioners
Journal title :
Applied Thermal Engineering
Journal title :
Applied Thermal Engineering