Title of article :
The chilled water storage analysis for a university building cooling system
Author/Authors :
Somkiat Boonnasa، نويسنده , , Pichai Namprakai، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Pages :
13
From page :
1396
To page :
1408
Abstract :
In this paper, a methodology is presented to determine the optimal chilled water storage (CWS) capacity and corresponding operating strategy for the air conditioning loads for different electricity tariff. Several scenarios were studied for the KMUTNB air conditioning system. It was concluded that the CWS with a chiller of 450 RT (2 units) running continuously, thermal-energy storage of 9413 RT-h and 5175 m3 volume was most suitable. The mechanical chiller (MAC) capacity and peak demand could be decreased by over 2 times and 31.2% respectively. It can move the energy consumption from the on peak to the off peak periods by 35.7%. The economics result showed PB, IRR and NPV are 10 y, 21% and 0.834 MUS$ compared with the existing system.
Keywords :
Chilled water storage , Peak demand reduction , Partial storage-load leveling , economics , Electric cost saving
Journal title :
Applied Thermal Engineering
Serial Year :
2010
Journal title :
Applied Thermal Engineering
Record number :
1045186