Title of article :
Residential heat pump heating performance with single faults imposed
Author/Authors :
Seok Ho Yoon، نويسنده , , W. Vance Payne، نويسنده , , Piotr A. Domanski، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
7
From page :
765
To page :
771
Abstract :
A heat pump equipped with a thermostatic expansion valve (TXV) was tested in environmental chambers during steady-state no-fault and imposed-fault operation. The studied system was an R410A split residential heat pump with an 8.8 kW nominal cooling capacity, Seasonal Energy Efficiency Ratio (SEER) of 13, and Heating Seasonal Performance Factor (HSPF) of 7.8. The imposed faults were compressor valve leakage, outdoor improper air flow, indoor improper air flow, liquid line restriction, refrigerant undercharge, and refrigerant overcharge. Evaporator fouling, condenser fouling, and refrigerant overcharge caused the greatest performance degradation. We observed substantial commonality between sensitive features in the heating and cooling modes; however, several different features were identified for the heating mode as more sensitive.
Keywords :
Thermostatic expansion valve , Heat pump , Heating mode , Fault detection and diagnosis
Journal title :
Applied Thermal Engineering
Serial Year :
2011
Journal title :
Applied Thermal Engineering
Record number :
1045454
Link To Document :
بازگشت