• Title of article

    INSULATION FAULT DIAGNOSIS IN HIGH VOLTAGE POWER TRANSFORMERS BY MEANS OF LEAKAGE FLUX ANALYSIS

  • Author/Authors

    By M. F. Cabanas، نويسنده , , F. Pedrayes Gonz?lez، نويسنده , , M. G. Melero، نويسنده , , C. H. Rojas Garc?a، نويسنده , , G. A. Orcajo، نويسنده , , J. M. Cano Rodr?guez، نويسنده , , and J. G. Norniella ، نويسنده ,

  • Issue Information
    ماهنامه با شماره پیاپی سال 2011
  • Pages
    24
  • From page
    211
  • To page
    234
  • Abstract
    Power transformers in service are subjected to a wide variety of electrical, mechanical and thermal stresses capable of producing insulation faults. This type of failure figures amongst the most costly faults in distribution networks since it produces both machine outage and electrical supply interruption. Major research effort has therefore focused on the early detection of faults in the insulating systems of large high voltage power transformers. Although several industrial methods exist for the on-line and off-line monitoring of power transformers, all of them are expensive and complex, and require the use of specific electronic instrumentation. For these reasons, this paper will present the On-Line analysis of transformer leakage flux as an efficient alternative for assessing machine integrity and detecting the presence of insulating failures during their earliest stages. An industrial 400 kVA-20 kV/400V transformer will be used for the experimental study. Very cheap, simple sensors, based on air core coils, will be used to measure the leakage flux of the transformer, and non-destructive tests will also be applied to the machine in order to analyse pre- and post-failure voltages induced in the coils.
  • Journal title
    Progress In Electromagnetics Research
  • Serial Year
    2011
  • Journal title
    Progress In Electromagnetics Research
  • Record number

    1052600