Title of article :
Experimental investigation on ammonia spray evaporator with triangular-pitch plain-tube bundle, Part II: evaporator performance
Author/Authors :
S. X. Zeng، نويسنده , , M.-C. Chyu ، نويسنده , , Z.H. Ayub، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2001
Pages :
12
From page :
2081
To page :
2092
Abstract :
Spray evaporation of ammonia was tested using spray nozzles distributing liquid ammonia downward onto a horizontal, 3–2–3 triangular-pitch, 1.25 pitch ratio, plain-tube bundle composed of stainless-steel tubes of 19 mm (0.75 in.) diameter. The saturation temperature test range was from −23°C to 10°C, and the heat flux range from 3.2 to 35 kW/m2. The effects of heat flux, saturation temperature, spray flow rate, nozzle height, and nozzle type (standard-angle or wide-angle) were investigated. The spray evaporation heat transfer performance was compared with that of pool boiling, as well as spray evaporation on square-pitch tube bundle and single tube.
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year :
2001
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number :
1070449
Link To Document :
بازگشت