• Title of article

    A numerical investigation of louvered fin-and-tube heat exchangers having circular and oval tube configurations

  • Author/Authors

    Jin-Sheng Leu، نويسنده , , Min-Sheng Liu، نويسنده , , Jane-Sunn Liaw، نويسنده , , Chi-Chuan Wang، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2001
  • Pages
    9
  • From page
    4235
  • To page
    4243
  • Abstract
    A numerical investigation of the airside performance for fin-and-tube heat exchanger having circular and oval configuration is presented in this study. The geometrical parameters of louver angle, louver pitch, and louver length are examined. For a fixed louver length (6.25 mm) and louver angle (14°), a 10% decrease of heat transfer performance is observed and a 41% decrease of pressure drop is seen for oval tube configuration. The calculated results indicate that the pressure drops always with increase in louver angle. However, an optimal value of heat transfer performance is observed due to the difference in the development of thermal boundary layer on the upper and lower louver surface. Both the heat transfer and friction performance increase with louver length. However, the rate of the increase of heat transfer performance is about the same as the increase of pressure drops.
  • Keywords
    Fin-and-tube heat exchanger , Louver fin , Oval tube
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Serial Year
    2001
  • Journal title
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
  • Record number