Title of article :
Metal foam heat sink for transmission window
Author/Authors :
G. Hetsroni، نويسنده , , M. Gurevich، نويسنده , , R. Rozenblit، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
11
From page :
3793
To page :
3803
Abstract :
A cooling device for transmission window of an accelerator based on aluminum foam with an inner heat production was investigated experimentally. Dissipation of heat flux up to 0.25 kW/cm2 was obtained, by using porous metal with porosity of 40 pores per inch. Under these conditions, the difference between the temperatures of the wall and the bulk water did not exceed 45 K and the pressure difference per unit length was 20 bar/m. Image processing of thermal maps of the surface of the metal foam showed that boundary conditions with constant heat flux became more relevant for numerical model than those with constant temperature at high values of Reynolds numbers ReK based on the permeability.
Keywords :
Heat transfer , Transmission window , Metal foam , Drag reduction , Enhancement
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year :
2005
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number :
1072230
Link To Document :
بازگشت