Title of article
A new method for determining coupled heat and mass transfer coefficients between air and liquid desiccant
Author/Authors
Yonggao Yin، نويسنده , , Xiaosong Zhang، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2008
Pages
11
From page
3287
To page
3297
Abstract
This paper presented the characteristic of liquid desiccant dehumidification based on NTU–Le model. The results showed that the Lewis number Le had little effect on air outlet humidity ratio during desiccant solution dehumidification process. A new method called hD–Le separative evaluation method was developed for determining coupled heat and mass transfer coefficients between air and liquid desiccant, through which the heat and mass transfer coefficients between air and liquid desiccant were calculated to obtain from experimental inlet and outlet parameters of air and desiccant solution. The effects of the air volume flow rate, temperature, humidity ratio and the solution concentration, temperature on the Lewis number, heat and mass transfer coefficient were analyzed according to experimental data and the hD–Le separative evaluation method. Based on the computation results, it was concluded that the Lewis number greatly depended on the operation parameters and conditions of the air and desiccant. In addition, the correlations of the heat and mass transfer coefficients were developed. The additional 74 groups of experiments validated the developed correlations by comparison of air/solution parameters change with the calculation data.
Keywords
Mass transfer coefficient , Air dehumidification , Liquid desiccant , Heat transfer coefficient , Lewis number
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year
2008
Journal title
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number
1075464
Link To Document