Title of article :
Physical water treatment using RF electric fields for the mitigation of CaCO3 fouling in cooling water
Author/Authors :
Leonard D. Tijing، نويسنده , , Hang Young Kim، نويسنده , , Dong Hwan Lee، نويسنده , , Cheol Sang Kim، نويسنده , , Young I. Cho، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Abstract :
The present study investigated the feasibility of RF electrical fields in mitigating CaCO3 fouling in cooling water. Three different voltages and two frequencies were used for the RF electric fields produced directly in water with varying cold-side velocity. Artificial hard water was used. Fouling resistances for the PWT-treated cases decreased by 34–88% from the values for no-treatment cases, depending on the cold-side flow velocity. The results showed blunt crystal structures for the PWT-treated cases, while no-treatment cases had sharp and pointed crystal structures. The new PWT method using RF electric fields presents a valid tool to mitigate CaCO3 fouling in cooling water.
Keywords :
Physical water treatment , RF electric field , CaCO3 fouling , Fouling resistance
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER