Title of article :
Air-side heat transfer characteristics of flat plate finned-tube heat exchangers with large fin pitches under frosting conditions
Author/Authors :
Mooyeon Lee، نويسنده , , Yonghan Kim، نويسنده , , Hosung Lee، نويسنده , , Yongchan Kim، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Pages :
7
From page :
2655
To page :
2661
Abstract :
The air-side heat transfer characteristics of flat plate finned-tube heat exchangers were measured and analyzed by varying the fin pitch, number of tube rows, and tube alignment under frosting conditions. Two empirical correlations for predicting the j-factor were developed separately for the inline and the staggered tube alignment, respectively, as a function of the Reynolds number, Fourier number, number of tube rows, and dimensionless hydraulic diameter normalized by fin pitch. The average deviation of the predictions of the present correlations from the measured data was 1.31% for the inline tube alignment and 0.65% for the staggered tube alignment.
Keywords :
Finned-tube heat exchanger , Frost , j-factor , Pressure drop , correlation