Title of article :
Heat transfer performance of lithium bromide solution in falling film generator
Author/Authors :
Chengming Shi، نويسنده , , Qinghua Chen، نويسنده , , Tien-Chien Jen، نويسنده , , Wang Yang، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Pages :
5
From page :
3372
To page :
3376
Abstract :
hm=129.7712Win-0.8058qw0.2422Re-0.0856The comparison of falling film generator with immersed tube generator shows that the heat transfer coefficient is 4.37 times higher than that of immersed tube generator, which can significantly reduce the volume of the falling film generator. The volume of falling film generator is only 52.1% of the volume of immersed tube generator.
Keywords :
Lithium bromide solution , Falling film evaporating , Generator performance
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year :
2010
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number :
1076749
Link To Document :
بازگشت