Title of article :
Steady-state performance of a run-around membrane energy exchanger (RAMEE) for a range of outdoor air conditions
Author/Authors :
Howard B. Hemingson، نويسنده , , Carey J. Simonson، نويسنده , , Robert W. Besant، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Pages :
11
From page :
1814
To page :
1824
Abstract :
The steady-state performance of a run-around membrane energy exchanger (RAMEE) for a wide range of outdoor air conditions is presented here. The RAMEE is numerically simulated and the sensible and latent effectiveness values corresponding to the maximum total energy effectiveness for different outdoor air conditions are presented. The effectiveness values are shown to be very dependent on outdoor conditions which results in some effectiveness values exceeding 100% or being less than 0% for several of the outdoor air conditions investigated. The heat and moisture transfers are shown to influence the latent and sensible performances of the RAMEE, respectively.
Keywords :
Run-around exchanger , Semi-permeable membrane , Variable outdoor air conditions , Heat and moisture exchange
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Serial Year :
2011
Journal title :
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER
Record number :
1077194
Link To Document :
بازگشت