• Title of article

    A power transmissibility method for assessing the performance of vibration isolation of building services equipment

  • Author/Authors

    C.M. Mak، نويسنده , , Su Jianxin، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    19
  • From page
    1281
  • To page
    1299
  • Abstract
    Force transmissibility is commonly adopted in building services engineering to assess the performance of vibration isolation. However, it neglects the effect of floor mobility on structure-borne sound power transmitted from a vibratory machine to the floor/roof and the interactions among several contact points between the vibratory machine and the floor/roof. The problem that motivated this study is the occasional occurrence of unsatisfactory performance of vibration isolators observed in building services engineering. This problem may be due to the over-simplification of the vibratory problem in the usual definition of the un-damped force transmissibility or isolation efficiency commonly used in engineering practice. In this paper, use of a “power transmissibility”, which includes the effect of floor mobility and the interaction of all dynamic forces transmitted to the floor through the vibration isolators, is proposed.
  • Journal title
    Applied Acoustics
  • Serial Year
    2002
  • Journal title
    Applied Acoustics
  • Record number

    1170552