Abstract :
In order to evaluate accurately a station blackout (SBO) event frequency of a multi-unit nuclear power plant that has a shared alternate AC (AAC) power source, an approach has been developed which accommodates the complex inter-unit behavior of the shared AAC power source under multi-unit loss of offsite power conditions. The SBO frequency at a target unit of probabilistic safety assessment could be underestimated if the inter-unit dependency of the shared AAC power source is not properly modeled. The approach is illustrated for two cases, 2 units and 4 units at a single site, and generalized for a multi-unit site. Furthermore, the SBO frequency of the first unit of the 2-unit site is quantified. The methodology suggested in the present paper is believed to be very useful in evaluating the SBO frequency and the core damage frequency resulting from the SBO event. This approach is also applicable to the probabilistic evaluation of the other shared systems in a multi-unit nuclear power plant.
Keywords :
Swing diesel generator , Alternate AC power source , Station blackout , Loss of offsite power , Multi-unit nuclear power plant