Title of article :
Microorganisms and particles in AHU systems: Measurement and analysis
Author/Authors :
Z. Lu، نويسنده , , W.Z. Lu، نويسنده , , J.L. Zhang، نويسنده , , D.X. Sun، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2009
Pages :
5
From page :
694
To page :
698
Abstract :
In this study, for better understanding the practical removal effect of air handling unit (AHU) system on airborne microorganisms (including bacteria and fungus) and particles and microbial growth, the samples of microorganisms and particles in 10 air handling unit (AHU) systems including fan coils and indoor air were collected and analyzed in air and component surfaces of such systems in two large public buildings. It is found that the removal efficiency is of the highest for bacteria 73.9% and the lowest for particles (0.5–2 μm) 24.4%. The surface concentration of equipment bacteria is 29 CFU/cm2 and fungi 137 CFU/cm2. Five of 10 systems have higher fungi concentrations on air intake than that on diffuser. The results also show that the central air supply system with common components (e.g., pre-filter and bag filter) has difficulty to achieve/maintain good performance once microorganisms and particles exist, especially for particle size D ≤ 3.3 μm. The size distribution has large influence on removal efficiency. The microbial growth on surfaces of duct and equipment was noticed and may be transferred into indoor air. This will decrease the indoor air quality and lead to adverse health effect.
Keywords :
Airborne microorganisms , Airborne particles , AHU system , removal efficiency
Journal title :
Building and Environment
Serial Year :
2009
Journal title :
Building and Environment
Record number :
1217568
Link To Document :
بازگشت