• Title of article

    Effect of MRT variation on the energy consumption in a PMV-controlled office

  • Author/Authors

    Dong-Hwa Kang، نويسنده , , Paek Hyoun Mo، نويسنده , , Dong-Hee Choi، نويسنده , , Seung-Yeong Song، نويسنده , , Myoung-Souk Yeo، نويسنده , , Kwang-Woo Kim، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2010
  • Pages
    9
  • From page
    1914
  • To page
    1922
  • Abstract
    This paper investigates the energy-saving potential of a thermal comfort-controlled office building. A comparative simulation study between the thermal comfort control and conventional thermostatic control is conducted on a building with glass façades where changes in the outdoor temperature and solar radiation over the course of a day affect radiant temperature and thus thermal comfort. To evaluate the thermal performance in the comfort-controlled space, a PMV-based thermal comfort controller, which adjusts the set-point room temperature of the existing thermostatic controller according to the changes of environmental variables, is assumed. The results demonstrate that thermal comfort competes with energy saving in a conventional thermostatic-controlled space. However, it is suggested that thermal comfort control provides consistent thermal comfort as well as energy-saving effect. The results show that energy consumption in a thermal comfort-controlled space is more affected by a change in the mean radiant temperature than in the conventional thermostatic-controlled space. The energy-saving potential in the thermal comfort-controlled space increases with low mean radiant temperature conditions. Although the energy-saving potential is reduced under high mean radiant temperature conditions, it is suggested that thermal comfort control is still a reasonable strategy to achieve both thermal comfort and energy savings simultaneously.
  • Keywords
    Thermal comfort control , PMV , Mean radiant temperature , ENERGY SAVING
  • Journal title
    Building and Environment
  • Serial Year
    2010
  • Journal title
    Building and Environment
  • Record number

    1217965