Author/Authors :
V.S. Chithra، نويسنده , , S.M. Shiva Nagendra، نويسنده ,
Abstract :
In this study, indoor air quality parameters were investigated in a naturally ventilated school building located near an urban roadway in Chennai. Monitoring was done during the winter (34 days) and summer (26 days) of 2011. The mean value of indoor PM10, PM2.5, PM1 and CO concentrations were found to be 149 ± 69, 61 ± 29, 43 ± 24, 0.10 ± 0.18 and 95 ± 61, 32 ± 16, 18 ± 9 μg/m3, 0.11 ± 0.14 ppm, respectively for winter and summer seasons. PM data analysis indicated that the indoor PM10 (60% of time) and PM2.5 (27% of time) levels were often exceeding the National Ambient Air Quality Standards (NAAQS). The indoor –outdoor (I/O) ratios of PM10, PM2.5 and PM1 and CO were found to be 2.52 ± 2.71, 1.44 ± 0.67, 0.97 ± 0.18 and 0.51 ± 0.38, respectively. The high I/O value of PM10 concentration indicates significant contribution from the activities of occupants inside classroom. The low I/O values for finer PM fractions and CO concentrations confirm the vehicular emission contribution from the adjacent road. The influence of classroom occupancy, comfort parameters, outdoor traffic and meteorological parameters on indoor pollutant concentrations were also investigated. Results showed good correlation between PM with comfort and outdoor meteorological parameters.
Keywords :
CARBON MONOXIDE , Meteorology , Occupancy , Particulate matter , school , Traffic