Title of article :
Effect of void fraction models on the two-phase friction factor of R134a during condensation in vertical downward flow in a smooth tube
Author/Authors :
A.S. Dalkilic، نويسنده , , S. Laohalertdecha، نويسنده , , S. Wongwises، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2008
Pages :
7
From page :
921
To page :
927
Abstract :
The void fraction of R134a condensing inside a vertical smooth tube is experimentally investigated in this study. The vertical test section is a 0.5 m long countercurrent flow double tube heat exchanger with refrigerant flowing down the inner tube and cooling water flowing upward in the annulus. The inner tube is made from smooth copper tubing and has an 8.1 mm inner diameter. The test runs are done at an average saturated condensing temperature of 40 °C. The average qualities are between 0.8 and 0.99 while the mass fluxes are 300 kg m− 2s− 1 and the heat fluxes are between 22 and 39.8 kW m− 2. The void fractions are indirectly determined using relevant measured data together with various void fraction models and correlations reported in the open literature. The friction factors obtained from various void fraction models and correlations are compared with each other and also with those determined from graphical information provided by Bergelin et al. The effect of void fraction alteration on the momentum pressure drop is also presented.
Keywords :
Condensation , Friction factor , R134a , heat transfer , Void fraction , Downward flow
Journal title :
International Communications in Heat and Mass Transfer
Serial Year :
2008
Journal title :
International Communications in Heat and Mass Transfer
Record number :
1220352
Link To Document :
بازگشت