Title of article :
Experimental investigation of convective heat transfer and pressure loss in a round tube fitted with circular-ring turbulators
Author/Authors :
V. Kongkaitpaiboon، نويسنده , , K. Nanan، نويسنده , , S. Eiamsa-ard، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2010
Pages :
7
From page :
568
To page :
574
Abstract :
This paper presents the effect of the circular-ring turbulator (CRT) on the heat transfer and fluid friction characteristics in a heat exchanger tube. The experiments were conducted by insertion of CRTs with various geometries, including three different diameter ratios (DR = d/D = 0.5, 0.6 and 0.7) and three different pitch ratios (PR = p/D = 6, 8 and 12). During the test air at 27 °C was passed through the test tube which was controlled under uniform wall heat flux condition. The Reynolds number was varied from 4000 to 20,000. According to the experimental results, heat transfer rates in the tube fitted with CRTs are augmented around 57% to 195% compared to that in the plain tube, depending upon operating conditions. In addition, the results also reveal the CRT with the smallest pitch and diameter ratios offers the highest heat transfer rate in accompany with the largest pressure loss.
Keywords :
Friction factor , Circular-ring turbulator (CRT) , Turbulator , Thermal Performance , Heat transfer enhancement
Journal title :
International Communications in Heat and Mass Transfer
Serial Year :
2010
Journal title :
International Communications in Heat and Mass Transfer
Record number :
1220685
Link To Document :
بازگشت