Title of article :
Application of metal foams in air-cooled condensers for geothermal power plants: An optimization study
Author/Authors :
Mostafa Odabaee، نويسنده , , Kamel Hooman، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Abstract :
Optimized design of metal foam heat exchangers, as replacements for finned-tubes in air-cooled condensers of a geothermal power plant, is presented here. Two different optimization techniques, based on first and second law (of thermodynamics) are reported. While the former aims at the highest heat transfer rate with as low pressure drop as possible, the latter minimizes the generated entropy in the thermodynamic system. Interestingly, the two methods lead to the same optimal design. The new design has been compared to the conventional air-cooled condenser designed and optimized by using the commercially available software ASPEN. It is shown that while the heat transfer rate increases significantly (by an order of magnitude) compared to the finned-tube for the same main flow obstruction height, the pressure drop increase is within an acceptable range. Further comparison between the two systems are carried out, making use of Mahjoob and Vafaiʹs performance factor developed specifically for metal foam heat exchangers.
Keywords :
Metal foam heat exchangers , Geothermal power plants , Finned-Tube , Air-cooled condensers
Journal title :
International Communications in Heat and Mass Transfer
Journal title :
International Communications in Heat and Mass Transfer