Title of article :
Correlations for evaporation heat transfer coefficient and two-phase friction factor for R-134a flowing through horizontal corrugated tubes
Author/Authors :
Suriyan Laohalertdecha، نويسنده , , Ahmet Selim Dalkilic، نويسنده , , Somchai Wongwises، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2011
Abstract :
Correlations for the evaporation heat transfer coefficient and two-phase friction factor of R-134a flowing through horizontal corrugated tubes are proposed. In the present study, the test section is a horizontal counter-flow concentric tube-in-tube heat exchanger with R-134a flowing in the inner tube and hot water flowing in the annulus. Smooth tube and corrugated tubes with inner diameters of 8.7 mm and lengths of 2000 mm are used as the inner tube. The corrugation pitches are 5.08, 6.35, and 8.46 mm and the corrugation depths are 1, 1.25, and 1.5 mm, respectively. The outer tube is made from smooth copper tube with an inner diameter of 21.2 mm. The correlations presented are formed by using approximately 200 data points for five different corrugated tube geometries and are then proposed in terms of Nusselt number, equivalent Reynolds number, Prandtl number, corrugation pitch and depth, and inside diameter.
Keywords :
heat transfer , Two-phase friction factor , R-134a , corrugated tube , Temperature
Journal title :
International Communications in Heat and Mass Transfer
Journal title :
International Communications in Heat and Mass Transfer