• Title of article

    Improvement of heat transfer with perforated circular holes in finned tubes of air-cooled heat exchanger

  • Author/Authors

    Dong H. Lee، نويسنده , , Jin M. Jung، نويسنده , , Jong H. Ha، نويسنده , , Young I. Cho، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2012
  • Pages
    6
  • From page
    161
  • To page
    166
  • Abstract
    The present study investigated the effect of perforated circular finned-tube (PCFT) on the convective heat transfer performance of circular finned-tube heat exchangers. The air-side convective heat transfer coefficients increased by 3.55% and 3.31% for 2-hole and 4-hole PCFT cases, respectively. The increase in the convective heat transfer coefficient was related to the reduction of the recirculation region by introducing the perforations at the flow-separation locations on the finned tube. The pressure drop across the finned-tube bundles increased by 0.68% and 2.08% for the 2-hole PCFT and 4-hole PCFT cases, respectively. The greater pressure drop in the case of the 4-hole PCFT might be due to excessive flow disturbances produced by multiple perforations. The fin factor defined as the ratio of the % increase of the convective heat transfer coefficient and that of the pressure drop was 5.19 for the 2-hole PCFT case, whereas that was 1.59 for the 4-hole PCFT case.
  • Keywords
    finned tube , Perforation , Heat Exchanger , Circular fin
  • Journal title
    International Communications in Heat and Mass Transfer
  • Serial Year
    2012
  • Journal title
    International Communications in Heat and Mass Transfer
  • Record number

    1221070