Oil entrainment in vertical refrigerant piping
Author/Authors :
Kesim، نويسنده , , Sami Cem and Albayrak، نويسنده , , Kahraman and ?leri، نويسنده , , Arif، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2000
Abstract :
The aim of this study is to investigate the required refrigerant speed, hence minimum refrigeration load, for carrying the lubricating oil up in vertical sections of refrigerant lines. It is assumed that the downward flow of the thin oil layer over the inner surface of the riser due to gravity is to be balanced with the upward flow of the oil film due to the shear force created by the upward flow of the refrigerant vapor. Velocities are converted to refrigeration capacities by considering a saturated cycle between specified condenser and evaporator pressures. General relationships thus developed are enumerated for R134a by preparing minimum capacity tables for copper suction and discharge risers.
Keywords :
Vitesse , Vertical tube , Refrigerant , vapour , Oil return , Speed , CALCULATION , Refrigerating circuit , Circuit frigorifique , Tuyauterie , Tube vertical , Retour dיhuile , Frigorigène , Vapeur , Calcul , piping