• Title of article

    Experimental investigation on the drop-in performance of R407C as a substitute for R22 in a screw chiller with shell-and-tube heat exchangers

  • Author/Authors

    Lee، نويسنده , , D.-Y and Ahn، نويسنده , , Y and Kim، نويسنده , , Y and Kim، نويسنده , , Y and Chang، نويسنده , , Y.-S and Nam، نويسنده , , L، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2002
  • Pages
    11
  • From page
    575
  • To page
    585
  • Abstract
    A drop-in test of a mixed refrigerant R407C is performed in a commercial screw chiller with shell-and-tube heat exchangers originally designed for R22. The test results show a severe performance reduction when substituting the refrigerant from R22 to R407C. The reason for the performance reduction is analyzed comprehensively, and the influence of thermodynamic properties, compressor efficiency, and heat transfer is evaluated quantitatively. The major factor causing the performance reduction is assessed as the degradation of the heat transfer in using the mixed refrigerant, R407C. The heat transfer degradation in the evaporator is found to be larger and influences more on the chiller performance reduction. The performance reduction caused by the evaporator is approximately two times compared with that of the condenser.
  • Keywords
    Refrigerant , R22 , Substitute , R407C , Measurement , Refroidisseur dיeau , Compresseur à vis , Frigorigène , R22 , Performance , Substitut , R407C , Remplacement immédiat , Water chiller , Performance , Screw compressor , Mesure , Drop-in
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2002
  • Journal title
    International Journal of Refrigeration
  • Record number