Title of article :
Effect of inlet humidity condition on the air-side performance of an inclined brazed aluminum evaporator
Author/Authors :
Kim، نويسنده , , Man-Hoe and Song، نويسنده , , Sumin and Bullard، نويسنده , , Clark W.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2002
Pages :
10
From page :
611
To page :
620
Abstract :
The effect of air inlet humidity condition on the air-side heat transfer and pressure drop characteristics for an inclined brazed aluminum heat exchanger has been investigated experimentally. For a heat exchanger with a louver angle of 27°, fin pitch of 2.1 mm and flow depth of 27.9 mm, a series of tests are conducted for the air-side Reynolds numbers of 80–400, with variation of inlet humidity condition. The heat transfer data are obtained for wet condition only and the pressure drop data are measured for both dry and wet conditions. The inlet air temperature and relative humidity range are 12 °C and 60–90%, respectively. The inclination angles (θ) from the vertical position are 0, 14, 45, and 67° clockwise (leeward direction). The inclination angles affect moderately the sensible heat transfer coefficient for wet condition, and the pressure drops for both dry and wet conditions increase systematically with the inclination angle. The heat transfer and pressure drop characteristics under wet condition are not influenced substantially by the air inlet humidity for θ ⩽45°. The effect of the louver directions at the inlet and outlet of the inclined heat exchanger on the performance is also addressed.
Keywords :
Ailette , Géométrie , air humide , Mesure , heat transfer , Mass transfer , Air Cooler , Fin , Humid air , Measurement , Design , Performance , Transfert de chaleur , Transfert de masse , refroidisseur dיair , Performance
Journal title :
International Journal of Refrigeration
Serial Year :
2002
Journal title :
International Journal of Refrigeration
Record number :
1339449
Link To Document :
بازگشت