Influence of liquid refrigerant injection on the performance of an inverter-driven scroll compressor
Author/Authors :
Cho، نويسنده , , Honghyun and Chung، نويسنده , , Jin Taek and Kim، نويسنده , , Yongchan، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
8
From page :
87
To page :
94
Abstract :
The operation of a scroll compressor at high compression ratios can cause excessively high discharge temperatures, which can be detrimental to the reliability and efficiency of the compressor. In the present study, the performance of an inverter-driven scroll compressor with liquid refrigerant injection was measured with a variation of compressor frequency, injection pressure, and injection location. The influence of the liquid injection on the performance is presented as a function of operating parameters and injection location by comparing the results with those for the non-injection case. It was found that liquid injection under high frequency was very effective at attaining higher performance and reliability of the compressor, but injection under low frequency showed some disadvantages. For high frequency at a given injection ratio, the injection at α=180°, for an injection angle at an injection port, yielded slightly better performance of the compressor as compared to that at α=90°.
Keywords :
Injection intermèdiaire , Refrigerating compressor , injection , Performance , Essai , Test , compresseur frigorifique , Mesure , Vitesse variable , Variable Speed , Measurement , compresseur à spirale , Scroll compressor , Performance
Journal title :
International Journal of Refrigeration
Serial Year :
2003
Journal title :
International Journal of Refrigeration
Record number :
1339532
Link To Document :
بازگشت