A simple model for falling film absorption on vertical tubes in the presence of non-absorbables
Author/Authors :
Medrano، نويسنده , , Marc and Bourouis، نويسنده , , Mahmoud and Perez-Blanco، نويسنده , , Horacio and Coronas، نويسنده , , Alberto، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
9
From page :
108
To page :
116
Abstract :
Most water–lithium bromide (LiBr) absorption chillers have a purge system to remove non-absorbable gases that cause a reduction in cooling capacity. Generally, the non-absorbables are originated in corrosion/passivation processes inside the machine, but leaks can also be a source of concern. However, since leaks must be corrected immediately to avoid machine deterioration, this study is mostly aimed at the non-absorbables evolved during operation. This paper analyses the effect of inlet non-absorbable air concentration, outlet purge velocity, absorber pressure and cooling water temperature on the falling film absorption process inside a vertical tube absorber, based on a simple transport coefficient model. This model consists of three ordinary differential equations solved with as method for initial-value problem, and a set of auxiliary equations. The study shows that the effect of non-absorbables can be significant, and furthermore provides a quantitative framework to aid in purge design. The nominal working conditions in this study were a solution Reynolds number of 100, an absorber pressure of 1.3 kPa, a cooling water temperature of 35 °C and an inlet solution concentration of 62% LiBr by weight. The results indicate that a minimum vapour velocity is required to sweep the non-absorbables along the absorber towards the purge, thus preventing reduced absorption fluxes. At a cooling water temperature of 35 °C, an inlet air concentration of 20% (by mole) resulted in a 61% reduction in mass absorption flux.
Keywords :
Système à absorption , Tube vertical , ABSORPTION , Film tombant , Absorber , Absorption System , Falling Film , Non-absorbable gas , Modelling , ABSORPTION , Absorbeur , Verticle tube , Modélisation , Gaz non condensable
Journal title :
International Journal of Refrigeration
Serial Year :
2003
Journal title :
International Journal of Refrigeration
Record number :
1339534
Link To Document :
بازگشت