Title of article :
Natural working fluids for solar-boosted heat pumps
Author/Authors :
Chaichana، نويسنده , , C and Aye، نويسنده , , Lu and Charters، نويسنده , , W.W.S، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Pages :
7
From page :
637
To page :
643
Abstract :
The option of using natural working fluids as a substitute of R-22 for solar-boosted heat pumps depends not only upon thermal performance and hazardous rating but also on potential impacts on the environment. This paper presents the comparative assessment of natural working fluids with R-22 in terms of their characteristics and thermophysical properties, and thermal performance. Some justification is given for using natural working fluids in a solar boosted heat pump water heater. The results show that R-744 is not suitable for solar-boosted heat pumps because of its low critical temperature and high operational pressures. On the other hand, R-717 seems to be a more appropriate substitute in terms of operational parameters and overall performance. However, major changes in the heat pumps are required. R-290 and R-1270 are identified as candidates for direct drop-in substitutes for R-22.
Keywords :
ةnergie solaire , Pompe à chaleur , Frigorigène , Substitut , Propane , Propylène , Solar energy , Heat pump , Rice , Replacement , Refrigerant , Carbon dioxide , Propane , Propylene , RIZ , Dioxyde de carbone
Journal title :
International Journal of Refrigeration
Serial Year :
2003
Journal title :
International Journal of Refrigeration
Record number :
1339597
Link To Document :
بازگشت