Title of article :
Effects of synthetic oil in a compression refrigeration system using R410A. Part I: modelling of the whole system and analysis of its response to an increase in the amount of circulating oil
Author/Authors :
Lottin، نويسنده , , O and Guillemet، نويسنده , , P and Lebreton، نويسنده , , Jean-Marc، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2003
Abstract :
Results concerning a model of vapour compression refrigeration system using R410A, a binary HFC blend, and designed to take into account the effects of the oil rejected by the compressor, are presented. These effects are negligible when the lubricant does not exceed 0.5% of the total refrigerant weight; above this value, the performances of the system decrease significantly.
Keywords :
R410A , Lubrifiant , Huile de synthèse , Fonctionnement , Frigorigène , Refrigerating compressor , Operating , Lubricant , Refrigerant , Synthetic oil , compresseur frigorifique , Modelling , R410A , Modélisation
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration