Title of article :
Influence of liquid receiver on the performance of reversible heat pumps using refrigerant mixtures
Author/Authors :
Rajapaksha، نويسنده , , Leelananda and Suen، نويسنده , , K.O، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
10
From page :
53
To page :
62
Abstract :
A liquid receiver is normally included in reversible vapour compression heat pumps (RHPs) to temporarily store the excess refrigerant charge occurring due to change of operation mode. The presence of a liquid receiver influences the total amount of refrigerant charged into a system, and particularly when using refrigerant mixtures, could affect the system circulation composition. Using a computer simulation, this paper compares the performance of RHPs designed with and without a liquid receiver, when using R407C. It was shown that the presence of a receiver caused an increase in the positive shift in the circulating composition, resulting in improved capacity while reducing the system COP in both heating and cooling modes when compared to a system without a receiver.
Keywords :
Modelling , receiver , liquid , R-407C , Transient regime , Modélisation , Pompe à chaleur , Réservoir , Performance , liquide , R-407C , Régime transitoire , Heat pump , Performance
Journal title :
International Journal of Refrigeration
Serial Year :
2004
Journal title :
International Journal of Refrigeration
Record number :
1339648
Link To Document :
بازگشت