    Flash gas bypass for improving the performance of transcritical R744 systems that use microchannel evaporators

  • Author/Authors

    Elbel، نويسنده , , Stefan and Hrnjak، نويسنده , , Pega، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2004
  • Pages
    12
  • From page
    724
  • To page
    735
  • Abstract
    The performance of transcritical R744 systems with direct expansion (DX) can be significantly improved by implementing a Flash Gas Bypass (FGB). The idea behind the concept is to bypass refrigerant vapor, created during the isenthalpic expansion process, around the evaporator. By feeding the evaporator with liquid refrigerant, pressure drop is reduced and refrigerant distribution is improved. With R744 as the working fluid, increased refrigerant-side heat transfer coefficients are expected as well. In addition, the FGB concept proves to be beneficial in terms of system design, in particular for combined air-conditioning and heat pumping applications. An experimental comparison to a conventional DX-system reveals that FGB increases the cooling capacity and COP at the same time by up to 9 and 7%, respectively. Even larger improvements are possible in case a variable speed compressor is utilized to match the performance of the conventional DX-system. A simulation model helps to separate the individual improvement mechanisms. It was found that the reduction of refrigerant-side pressure drop is the dominant improvement mechanism of FGB.
  • Keywords
    Transcritical cycle , Design , Refrigerating circuit , EXPANSION , Conception , R744 , Cycle transcritique , Circuit frigorifique , Détente , R744 , Carbon dioxide , Dioxyde de carbon
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2004
  • Journal title
    International Journal of Refrigeration
  • Record number

    1339734