Title of article :
A comprehensive design and performance evaluation study of counter flow wet cooling towers
Author/Authors :
Khan، نويسنده , , Jameel-Ur-Rehman and Qureshi، نويسنده , , Bilal Ahmed and Zubair، نويسنده , , Syed M.، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2004
Pages :
10
From page :
914
To page :
923
Abstract :
Fouling of cooling tower fills is one of the most important factors affecting its thermal performance, which reduces cooling tower effectiveness and capability with time. In this paper, the fouling model presented in an earlier paper using the experimental data on fill fouling, is used to investigate the risk based thermal performance of the cooling tower. It is demonstrated that effectiveness of the cooling tower degrades significantly with time indicating that for a low risk level (p=0.01), there is about 6.0% decrease in effectiveness for the given fouling model. The sensitivity analysis of the cooling tower is investigated for both rating and design calculation for different values of mass flow rate ratios. The effect of atmospheric pressure on the thermal performance of the cooling tower is also demonstrated.
Keywords :
Tour de refroidissement , Calcul , Performance , Encrassement , Design , Cooling Tower , Performance , FOULING , Conception , CALCULATION
Journal title :
International Journal of Refrigeration
Serial Year :
2004
Journal title :
International Journal of Refrigeration
Record number :
1339762
Link To Document :
بازگشت