Title of article
Optimum control of the gas overheat in the evaporator of a vapour compression refrigeration system when the refrigerant is polluted
Author/Authors
Lottin، نويسنده , , Olivier، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2004
Pages
4
From page
1003
To page
1006
Abstract
Results concerning the response of a refrigeration system simulation software to an increase in the amount of oil flowing with the refrigerant are presented. It is shown that there are optima of the apparent overheat value, for which either the exchanged power or the refrigeration coefficient of performance (COP) is maximised: consequently, it is not possible to optimise both the refrigeration COP and the evaporator power. However, in most of the cases (i.e. contents of circulating lubricant), the optimal values of the apparent overheat are below the values that the expansion valves usually impose.
Keywords
Me´lange binaire , Huile , Compression system , Evaporator , surchauffe , Overheat , Refrigerant , Oil , Frigorige`ne , Evaporateur , Optimisation , Binary mixture , Syste`me a` compression , optimization