Title of article :
Comparison of performances of displacement and mixing ventilations. Part I: thermal comfort
Author/Authors :
Lin، نويسنده , , Zhang and Chow، نويسنده , , T.T. and Fong، نويسنده , , K.F. and Wang، نويسنده , , Qiuwang and Li، نويسنده , , Ying، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
12
From page :
276
To page :
287
Abstract :
A numerical simulation using a validated Computational Fluid Dynamics (CFD) model of several types of buildings was used to investigate the difference between mixing and displacement ventilation (DV). The comparison of performances of displacement and mixing ventilations (MV) will be reported in two parts, one on thermal comfort and the other one on indoor air quality. This paper, i.e., Part I, compares the performances of floor-supply DV systems with traditional MV systems for offices, classrooms, retail shops and industrial workshops under a wide range of Hong Kong thermal and flow boundary conditions, such as a very high cooling load. Through proper design, DV can maintain a thermally comfortable environment that has a low air velocity, a small temperature difference between the head and ankle level, and a low percentage of dissatisfied people.
Keywords :
Confort , air conditioning , ventilation , Residential building , CALCULATION , Performance , Comfort , Immeuble dיhabitation , ventilation , SIMULATION , Calcul , Performance , Conditionnement dיair , SIMULATION
Journal title :
International Journal of Refrigeration
Serial Year :
2005
Journal title :
International Journal of Refrigeration
Record number :
1339821
Link To Document :
بازگشت