Abstract :
Evaporative cooling is used in industrial and air conditioning processes to reduce temperature in different fluids. Direct evaporation systems can lead to environmental problems such as Legionnaireʹs disease, and indirect systems reduce system efficiency.
ork presents the manufacture, test bed set up and trials carried out on a ceramic evaporative cooling system which acts as a semi-indirect cooler. Depending on air characteristics, it may act as a sensible or enthalpic exchanger. The water cooled in a cooling tower, using the return air coming from the conditioned room (22 °C and 50% comfort conditions) goes through the ceramic pipes, exchanging sensible and latent heat with a current of outdoor air.
e of this recovery system is mainly in climates with a high temperature and humidity such as tropical environments where the system yields a decrease in supply air humidity, using the cooling power of return air.
sts presented show the system behaviour for various supply air conditions.
Keywords :
Expérimentation , Transfert de chaleur , Transfert de masse , air conditioning , Evaporative system , Ceramic , Tube , Experiment , Mass transfer , heat transfer , Conditionnement dיair , Système évaporatif , Tube , Céramique
Journal title :
International Journal of Refrigeration
Journal title :
International Journal of Refrigeration