Title of article :
Flow fields in shell-and-tube condensers: comparison of a pure refrigerant and a binary mixture
Author/Authors :
Karlsson، نويسنده , , Tord and Vamling، نويسنده , , Lennart، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
8
From page :
706
To page :
713
Abstract :
Detailed 2D CFD calculations for vapour flow field and rate of condensation are carried out for a geometry similar to a real shell-and-tube condenser with 100 tubes, with condensation on the shell-side. The differences in vapour flow behaviour are investigated for pure R22 and for a binary mixture of R32 and R134a, which has a gliding temperature difference of 5.5 K. It is shown that, the flow field for a zeotropic mixture is significantly different from that for a pure fluid. The nature of the mixture flow causes the vapour and condensate to flow counter-currently in part of the condenser. Adjustments of the inlet design turn out to influence the rate of heat transfer by up to 24% for the conditions tested, with greater influence on heat transfer for lower driving forces.
Keywords :
R32 , R134a , Zeotropic mixture , ةcoulement , Vapeur , Frigorigène , comparaison , R22 , Condenser , R32 , Mélange non azéotropique , Flow , R134a , Refrigerant , vapour , R22 , comparison , Condenseur à eau
Journal title :
International Journal of Refrigeration
Serial Year :
2005
Journal title :
International Journal of Refrigeration
Record number :
1339928
Link To Document :
بازگشت