Title of article :
Effects of refrigerant charge amount on the performance of a transcritical CO2 heat pump
Author/Authors :
Cho، نويسنده , , Honghyun and Ryu، نويسنده , , Changgi and Kim، نويسنده , , Yongchan and Kim، نويسنده , , Ho Young، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2005
Pages :
8
From page :
1266
To page :
1273
Abstract :
A typical transcritical CO2 system shows lower performance than conventional air conditioners in cooling mode operation. In addition, the CO2 system shows a large variation of the performance according to refrigerant charge whereas the conventional systems do not show large variation. In this study, the performance of the CO2 heat pump was measured and analyzed by varying the refrigerant charge amount at standard cooling condition. In addition, the performance sensitivity of the CO2 system as a function of refrigerant charge was compared to those for the R22, R410A, and R407C systems. The cooling COP of the CO2 system was reduced more significantly at undercharged conditions than at overcharged conditions as the deviation from the optimal charge increased. The expansion loss was the dominant factor affecting system performance at undercharged conditions, while the gascooler loss became the major parameter at overcharged conditions. Among the systems investigated and compared in this study, the CO2 system showed the most reduction in performance at undercharged conditions.
Keywords :
CO2 , Transcritical cycle , Experiment , Performance , Parameter , Refrigerant charge , CO2 , Pompe à chaleur , Cycle transcritique , Expérimentation , Performance , Paramètre , Charge en frigorigène , Heat pump
Journal title :
International Journal of Refrigeration
Serial Year :
2005
Journal title :
International Journal of Refrigeration
Record number :
1340186
Link To Document :
بازگشت