• Title of article

    The application of photo-coupler for frost detecting in an air-source heat pump

  • Author/Authors

    Byun، نويسنده , , Ju-Suk and Jeon، نويسنده , , Chang-Duk and Jung، نويسنده , , Ji-Hoon and Lee، نويسنده , , Jinho، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2006
  • Pages
    8
  • From page
    191
  • To page
    198
  • Abstract
    This experimental study is carried out to investigate reliability and effectiveness of a new method of using photo-coupler for detecting frost formation in an air source heat pump, and further to determine the most efficient initiation point of the defrost cycle. This new method of using photo-coupler as a frost sensing device is evaluated by comparing its performance with conventional time control defrost system in which defrost cycle is set to start at predetermined interval, e.g. about at every 1–1.5 h. Results indicate that overall heating capacity of photo-coupler detection method (case IV) is 5.5% higher than that of time control method. It is also shown that for maximum efficiency the defrost cycle must be initiated before the frost build-up area exceeds 45% of total front surface of the outdoor coil.
  • Keywords
    frost , Pompe à chaleur , Air-air , Croissance , Expérimentation , Optique , Procédé , Heat pump , Experiment , Growth , Air-air , optical , Process , givre
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2006
  • Journal title
    International Journal of Refrigeration
  • Record number