Title of article
Dynamic behavior of a direct expansion evaporator under frosting condition. Part I. Distributed model
Author/Authors
Tso، نويسنده , , C.P. and Cheng، نويسنده , , Y.C. and Lai، نويسنده , , A.C.K.، نويسنده ,
Issue Information
روزنامه با شماره پیاپی سال 2006
Pages
13
From page
611
To page
623
Abstract
A general distributed model with two-phase flow for refrigerant coupled with a frost model is developed for studying the dynamic behavior of an evaporator. The equations are derived in non-steady-state manner for the refrigerant and a quasi-steady state model with permeation for the frost. The complex flow and geometry of the finned tube evaporator lead to uneven wall and air temperature distributions, which in turn affect the rate of frost growth and densification along the coil depth. Results include frost accumulation and its effect on energy transfer, air off-coil temperature, refrigerant liquid dry-out position and propagation of frost formation along the coil.
Keywords
Two-phase flow , Frost formation , Temperature , heat transfer , Conditionnement dיair , air conditioning , Température , Givrage , ةvaporateur , Evaporator , tube aileté , Refrigeration , Transfert de chaleur , Froid , Modelling , finned tube , Modélisation , ةcoulement diphasique
Journal title
International Journal of Refrigeration
Serial Year
2006
Journal title
International Journal of Refrigeration
Record number
1341200
Link To Document