• Title of article

    Frost, defrost, and refrost and its impact on the air-side thermal-hydraulic performance of louvered-fin, flat-tube heat exchangers

  • Author/Authors

    Xia، نويسنده , , Y. and Zhong، نويسنده , , Y. and Hrnjak، نويسنده , , P.S. and Jacobi، نويسنده , , A.M.، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2006
  • Pages
    14
  • From page
    1066
  • To page
    1079
  • Abstract
    The thermal-hydraulic performance under conditions of an initial frost growth on the air-side surface, and for subsequent ‘refrosting’ after a defrost period is experimentally studied for folded-louvered-fin, microchannel heat exchangers. In total, five heat exchangers are considered; the thermal performances during one frost-growth cycle for four different fin geometries are compared in terms of overall heat transfer coefficient, pressure drop, and j and f factors; the defrost and refrost characteristics of two heat exchangers are compared to explore geometry effects. Typically, the performance under refrosting conditions becomes periodic and repeatable after the third or fourth refrosting cycle. The allowable frost growth period (before a defrost is required), the defrost requirement, and the thermal-hydraulic performance depend on heat exchanger geometry for the specimens used in this study.
  • Keywords
    Air Cooler , Frost formation , finned tube , Defrost , Experiment , heat transfer , ةchangeur de chaleur , refroidisseur dיair , tube aileté , Dégivrage , Expérimentation , Chute de pression , Transfert de chaleur , Givrage , Pressure drop , Heat Exchanger
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2006
  • Journal title
    International Journal of Refrigeration
  • Record number

    1341341