• Title of article

    Two-phase split of refrigerants at a T-junction

  • Author/Authors

    Tae، نويسنده , , Sang-Jin and Cho، نويسنده , , Keumnam، نويسنده ,

  • Issue Information
    روزنامه با شماره پیاپی سال 2006
  • Pages
    10
  • From page
    1128
  • To page
    1137
  • Abstract
    The present study experimentally investigated the two-phase flow split of refrigerants at a T-junction. As geometric parameters, the direction of the inlet or branch tube and the tube diameter ratio of branch to inlet tube were chosen. As inlet flow parameters, the inlet mass flux and quality were varied from 100 to 700 kg m−2 s−1 and from 0.1 to 0.9, respectively, for the condition of distribution header of a multi-pass evaporator in the general refrigeration system. All experiments were performed for R-22, R-134a, and R-410A. The measured data were compared with the values predicted by the models developed for air–water or steam–water mixture in the literature. We propose a modified model for application to the reduced T-junction and vertical orientation of tubes. Among the geometric parameters, the branch tube direction showed the largest sensitivity to the mass flow rate ratio for the gas phase, while the inlet quality showed the largest sensitivity to the mass flow rate ratio among the inlet flow parameters.
  • Keywords
    Two-phase flow , Expérimentation , Pipe , Gaz , Shape , liquide , Experiment , Flow , GAS , liquid , Frigorigène , R22 , R134a , R410A , Refrigerant , ةcoulement diphasique , R22 , Raccordement , R134a , Tuyauterie , R410A , Géométrie , junction , débit
  • Journal title
    International Journal of Refrigeration
  • Serial Year
    2006
  • Journal title
    International Journal of Refrigeration
  • Record number