Title of article :
A DDC-based capacity controller of a direct expansion (DX) air conditioning (A/C) unit for simultaneous indoor air temperature and humidity control – Part II: Further development of the controller to improve control sensitivity
Author/Authors :
Li، نويسنده , , Zheng-hua Deng، نويسنده , , Shiming، نويسنده ,
Issue Information :
روزنامه با شماره پیاپی سال 2007
Pages :
10
From page :
124
To page :
133
Abstract :
The development of the novel direct digital control (DDC)-based capacity controller for a direct expansion (DX) air conditioning (A/C) unit having variable-speed compressor and supply fan to simultaneously control indoor air temperature and relative humidity (RH) in a conditioned space served by the DX A/C unit has been reported in Part I of the two-part series. The results of preliminary controllability tests for the novel capacity controller presented in Part I, however, suggested that the controller developed was operational, with acceptable control accuracy but rooms for improvement with respect to control sensitivity. This paper, the second part of the two-part series, reports on the further development of the controller to improve its control sensitivity and the associated controllability test results. Both control accuracy and reasonable control sensitivity were achieved by incorporating a traditional Proportional–integral (PI) controller into the DDC-based capacity controller.
Keywords :
Variable Speed , Design , REGULATION , Capacity reduction , Improvement , Conditionnement dיair , Système à compression , Système frigorifique , Conception , Vitesse variable , Réduction de capacité , Régulation , air conditioning , Expérimentation , Compression system , Refrigeration system , Amélioration , Experiment
Journal title :
International Journal of Refrigeration
Serial Year :
2007
Journal title :
International Journal of Refrigeration
Record number :
1341533
Link To Document :
بازگشت